| ALL |
- Never connect a low voltage thermostat to line voltage.
|
Five wires control a Heat Pump with an auxiliary heat stage. They were labeled:
G, Y, R or RH or RC, and W or W2.
Either B or O was used. |
- Do not connect wires to both B and O. Connect the reversing valve wire to B or O, just as the previous thermostat. Connect 24 VAC wire to R. Connect compressor wire to Y, fan wire to G, and auxiliary wire to W2. Add jumper from W2 to E. It is not necessary to wire the X terminal.
|
Six wires control a Heat Pump with an auxiliary heat stage. They were labeled:
G, Y, R or RH or RC, and W or W2.
Either B or O was used.
And Emergency wire E is present. |
- Do not connect wires to both B and O. Connect the reversing valve wire to B or O, just as the previous thermostat. Connect 24 VAC wire to R. Connect compressor wire to Y, fan wire to G, and auxiliary wire to AUX. Connect Emergency Heat wire E. It is not necessary to wire the X terminal.
|
| For further assistance |
- Contact your HVAC service company or our Technical Assistance Line if not resolved.
|